NRC2400-A1-20-ST1
MFG Part Number 385911-015
Nextreme™ Performance Chiller
The Nextreme NRC2400 Recirculating Chiller features premium components and environmentally friendly refrigerants in a user-friendly design. It is designed to cool well below ambient and dissipate heat away from thermally sensitive equipment. Featuring variable speed motors for the compressor and condensing fan, the Nextreme NRC2400 offers a high coefficient of performance and low-noise operation. The Nextreme NRC2400 comes with several standard features and additional options allow for application-specific configurations. Power cord is not supplied with the unit and must be ordered separately.
Features
  • Precise Temperature Control
  • Compact Form Factor
  • Reliable Solid-State Operation
  • Intuitive GUI
  • Low Noise Operation




Cooling Power Operating Points
100% Water (20°C Ambient Air)
Cooling Power (Qc) = 2,800 Watts
Fluid Setpoint = 20 °C
Fluid ΔT @ 15.0 L/min = 2.7 °C

100% Water (30°C Ambient Air)
Cooling Power (Qc) = 2,600 Watts
Fluid Setpoint = 20 °C
Fluid ΔT @ 15.0 L/min = 2.5 °C

60/40 Water-Glycol (20°C Ambient Air)
Cooling Power (Qc) = 2,650 Watts
Fluid Setpoint = 20 °C
Fluid ΔT @ 15.0 L/min = 2.8 °C

60/40 Water-Glycol (30°C Ambient Air)
Cooling Power (Qc) = 2,450 Watts
Fluid Setpoint = 20 °C
Fluid ΔT @ 15.0 L/min = 2.6 °C

Select Graph




Technical Specifications
Performance
Nominal Cooling Capacity1
2,800 W
Setpoint Range
-10°C to 40°C
Temperature Stability3
±0.10°C
Nominal Operating Flowrate (60 Hz)1
15.0 L/min @ 2.6 Bar
Nominal Operating Flowrate (50 Hz)1
15.0 L/min @ 1.5 Bar
Refrigerant
R 513A
Sound Pressure Level at Nominal Cooling Capacity (50 Hz)1
65 dBA
Sound Pressure Level at Nominal Cooling Capacity (60 Hz)1
66 dBA
Operation
Coolant
Water or Water/Glycol
Operating Temperature2
15°C to 40°C
Storage temperature range (w/o coolant)
-25°C to 70°C
Humidity range
30% to 80%
Storage Humidity range
5% to 95%, non-condensing
Altitude
< 2,000 meters
Input Voltage
220 - 240 VAC
Frequency
50 / 60 Hz
Current
< 8.4 Amps
Maximum Forward Pressure
4.1 Bar
Compliance
ANSI / UL / CSA / IEC EN 61010-1 Edition 3
Physical
Height
750 mm
Length
520 mm
Width
480 mm
Weight
54 kg
Coolant Capacity
5 Liters
Couplings
1/2 in NPT
Standard Features
Variable Speed Motors
Variable speed compressor and condensing fans for quiet operation and improved energy efficiency.
Semi-Closed Fluid System
Sealed fluid system with breathable reservoir cap (similar to an automobile). This prevents evaporative loses, introduction of bacteria, and the need for components to prevent fluid from draining back into the system when installed below the application.
Optical Fluid Level Switch
Fluid level sensing with no moving parts.
RS-232 Communications
Complete control integration of chiller into higher level assembly control system.
Supply Pressure Sensing
Pressure sensing for applications sensitive to high operating conditions.
Accessory Kits
Feature
Kit Part Number
Description
Flow Control Valve and Flow Sensing Kit
387004277
Externally installed valve for reducing the overall flow to the application. Full flow continues through the chiller to maintain high heat transfer rates and temperature stability. Flow meter for measuring coolant flow rate. Installed external to the chiller with both a local display and connectivity to chiller LCD display.
Water Filter Kit
387004279
Hot swappable, 5-micron water filter for filtering particulates from the coolant circuit.
Cord Options

These power cords have been tested and validated on Nextreme devices.

Power cord is not supplied with the unit and must be ordered separately.

MFG Part Number
Plug Type
Standard
Style
Cable
Length
Rating
Color
Connector
Order
387005324
Universal
None
Flying Leads
2.0 m
250VAC, 16A* / 20A**
Black
C19

* IEC   ** UL



Notes
  1.  Nominal capacity rating is given at a 20°C (68°F) setpoint, 20°C (68°F) ambient temperature, sea level.
  2.  For ambient conditions outside this range, please contact Laird Thermal Systems.
  3.  Typical for nominal capacity rating. Contact LTS applications engineering for application specific performance.

Any information furnished by Laird and its agents, whether in specifications, data sheets, product catalogues or otherwise, is believed to be (but is not warranted as being) accurate and reliable, is provided for information only and does not form part of any contract with Laird. All specifications are subject to change without notice. Laird assumes no responsibility and disclaims all liability for losses or damages resulting from use of or reliance on this information. All Laird products are sold subject to the Laird Terms and Conditions of sale (including Laird’s limited warranty) in effect from time to time, a copy of which will be furnished upon request.

© Copyright 2024 Laird Thermal Systems, Inc. All rights reserved. Laird™, the Laird Ring Logo, and Laird Thermal Systems™ are trademarks or registered trademarks of Laird Limited or its subsidiaries.

Nextreme™ is a trademark of Laird Thermal Systems, Inc. All other marks are owned by their respective owners.

Revision: 03 Date: 11-24-2024

Print Date: 12-25-2024